FR Floatless Relay

Category

Description

HTM FR Floatless relays are versatile and compact floatless relays that are suitable for pumping system control and level alarm annunciations. Standard units are housed in DIN enclosures and can be configured as a controller for water supply or drainage control systems. HTM FR Floatless relays utilise a safe control voltage for level sensing via level electrodes located in the field.

Features

  • Built-in Lightning Surge Arrester HTM FR floatless relays are floatless relays truly designed for tropical environments where lightning surge is a major destructive factor in instrumentation. Each FR floatless relay has a built-in 2-stage lightning surge arrester which protects the controller in the event of a lightning surge. This effectively reduces the downtime of the relay.
  • Battery Operation FR floatless relays can be powered by 115, 230VAC, 12, 24, 48VDC and hence can be operated in solar-powered and battery-operated systems without the use of any power converter.
  • Indication Two state LED indicators for the indication of High (red/activated) and Low (green/deactivated).
  • Adjustable Sensitivity The sensitivity level of all HTM FR floatless relays is adjustable to suit different working conditions.

Application

PRINCIPLE OF OPERATION

HTM FR floatless relays are level controllers that detect water levels based on the conductivity of the medium measured by using conductive electrodes. When a relay senses the liquid level measured, the output contacts of the relay are energized and latched. These latched outputs are released when the latching electrode is brought out of the medium measured. The operation repeats as the medium’s level changes to achieve a continuous level control system.

Specifications

  • Sensing voltage: 10VDC
  • Output: 1 SPDT & 1 SPST
  • Contact rating: 1A @ 230VAC
  • Power supply:
    • VDC: 12, 24, 48
    • VAC: 110, 115, 220, 230
  • Casing: ABS shell, Polycarbonate Cover
  • Enclosure: IP10
  • Terminal size: 2.5mm² cable
  • Temperature: -10 to 60°C
  • Mounting: DIN rail or panel mount

WIRING DIAGRAM NOTES

  • Do not connect Lo Electrode if latching of Low level is not required.
  • All Dimensions in MM.

Dimensions & Connections